at the setpoint.
. 2 Integral Time for second output. Range: 0-3600 sec. Set at 0 for Integral off. After setting up
the proportional band, set the integral time at a high value and continue to decrease until the
system just starts to oscillate and then back off.
d 2 Derivative Time for second output. Range: 0-900 sec. Set at 0 for Derivative off. The purpose
of adjusting the derivative time is to reduce or eliminate overshoot. Set the derivative at a small
value then increase the set point. If the temperature overshoots, increase the derivative time in
small increments until overshoot is reduced. If the system becomes too sluggish, decrease the
derivative time.
Cyt 2 Proportional cycle for second output. Same as Cyt 1
HyS 2 Hysteresis for second output. Same as HyS 1
GAP1 Main Control Gap. Only used with second output. Set to turn off early when approaching the
setpoint.
GAP2 Sub Control Gap. Only used with second output. Set to turn on early when approaching the
setpoint.
LCK Lock Set Up.
• 0000 No locks on.
• 0100 Can only enter and edit levels 1 & 2.
• 0110 Can enter levels 1 & 2, but only edit level 1.
• 0001 Can only enter level 1 and edit setpoint.
• 0101 Everything is locked out except the lock parameter.
Level 3 Parameters
To access the level 3 parameters, make sure lock is set at 0000 (see level 2 instructions). Press the Set key
and the ? key and hold for five seconds. Pressing the Set key cycles through the parameters.
inP1 Selects the input device and range, see table 1 for complete range.
AnL1 Analog zero set
AnH1 Analog pan set.
dP Sets the position of the decimal point.
LSPL Lower setpoint limit. (Must be within the input range).
USPL Upper setpoin limit. (Must be within the input range)
Anl2 Analog zero set for second output (when ordered).
AnH2 Analog span set for second output (when ordered).
Ald1 Alarm mode (Alarm 1). See table 2 for modes available.
Alt1 Alarm 1 time mode. 0=flicker alarm, 99.59=continous alarm, in between setting=delay time.
Ald2 Alarm mode (Alarm 2). See table 2 for modes available.
Alt2 Alarm 2 time mode. 0=flicker alarm, 99.59=continous alarm, in between setting=delay time.
Ald3 Alarm mode (Alarm 3). See table 2 for modes available.
Alt3 Alarm 3 time mode. 0=flicker alarm, 99.59=continous alarm, in between setting=delay time.
HYSA Hysterisis of alarm, range 0-1000.
CLO1 Calibrate the low value of output. Range: lower-upper setpoint. (Current output only).
CHO1 Calibrate the high value of output. Range: lower-upper setpoint. (Current output only).
CLO2 Calibrate the low value of second output. Range: lower-upper setpoint. (Current output only).
CHO2 Calibrate the high value of second output. Range: lower-upper setpoint. (Current output only).
PUO5 Compensate PV
Unit Temperature units. C, F, A (analog)
SOFt Soft filter. Adjust the response time of PV. A larger value means faster response time. Range
0-5000. Set at 1000 for default.
OUd Action mode. Heat or cool.
OPAd Control action. PID or fuzzy.